Work the pump-panel math the way the certification exam teaches it: a friction loss calculator, a pump discharge pressure calculator, and nozzle-flow tools — every answer with the formula steps shown, so you learn the math instead of just getting a number.
This page is the free taster. The app adds saved apparatus profiles, standpipe and relay modules, and randomized driver/operator drills graded like the exam — $0.99 once, no ads, works offline.
FL = C × Q² × L — Q is the flow in hundreds of gpm, L is the hose length in hundreds of feet. Coefficients are the standard published IFSTA / National Fire Academy values.
Departments flow-test their own hose. If your tested coefficient differs from the textbook value, pick “Custom coefficient…” and use yours — tested hose on your rig governs.
PDP = nozzle pressure + friction loss + appliance loss ± elevation pressure. Elevation uses 0.434 psi per foot of height (one story ≈ 10 ft ≈ 4.3 psi; field rule of thumb: 5 psi per story).
IFSTA appliance allowance: under 350 gpm, appliance loss is insignificant (0 psi). At 350 gpm or more, allow 10 psi per appliance. Master stream appliances: 25 psi each, any flow.
Smooth-bore flow and nozzle reaction, plus fog-nozzle flow at off-rated pressures by the square-root law.
The same published standards Pump Ops Trainer teaches — IFSTA Pumping Apparatus Driver/Operator Handbook tradition and the NFPA 1002 driver/operator curriculum.
| Hose | C |
|---|---|
| 1″ booster | 150 |
| 1½″ | 24 |
| 1¾″ attack | 15.5 |
| 2″ | 8 |
| 2½″ | 2 |
| 3″ (2½″ couplings) | 0.8 |
| 3½″ | 0.34 |
| 4″ LDH | 0.2 |
| 5″ LDH | 0.08 |
Standard IFSTA / National Fire Academy coefficients. Tested hose varies — many departments publish their own tested values, and those govern. Sources consulted for every constant on this page: IFSTA / National Fire Academy friction-loss coefficient tables and appliance allowances; Fire Engineering, “Every Pump Operator's Basic Equation” (Spurgeon); TFT, “Hydraulic Calculations Every Firefighter Needs to Know.”
Pump Ops Trainer turns this math into a coach: save your rigs and preconnects once, then drill friction loss, pump pressure, nozzle flow, elevation, relay and standpipe problems graded on the certification-style windows — with a full worked solution after every answer.
Also from Mergify Studios for the fire service: Mayday Trainer — mayday and LUNAR-report practice drills; and Pocket Rescue — CPR & first-aid steps for the worst minute.
TRAINING AID ONLY. This page teaches and drills pump-operator math using the standard published formulas. It is not a substitute for your department's SOPs, your apparatus pump charts and placards, manufacturer ratings, or the judgment of a qualified driver/operator on the fireground. Always verify pressures against your own flow-tested hose and equipment. Do not use this page to direct live emergency operations.